Oerlikon battery 12V

Montana, Pretoria, Gauteng Added at 09:19, 19 September 2016, Ad ID: 1005524687

Offer from Individual
Condition Used
Year 2015
 

Battery was gift from friend brand new never been used . i used it for 4 months. The battery floats 12.79v.

Detail
Type :12CP150
Part number: 663 - show phone - 0

Electrical Data:

Nominal voltage :12 V
Number of cells:6
Rated capacity C:10 to 1.80 Vpc at 20 °C 150 Ah
Rated capacity C:8to 1.75 Vpc at 25 °C 150 Ah
Current/Power for 0.5 h back-up time 1.65 Vpc 20 °C :185 A ,2034 W
Current/Power for 1.0 h back-up time 1.67 Vpc 20 °C :107 A ,1200 W
Current/Power for 2.0 h back-up time 1.80 Vpc 20 °C :58.2 A ,672 W
Current/Power for 4.0 h back-up time 1.80 Vpc 20 °C :32.7 A ,381 W
Current/Power for 8.0 h back-up time 1.80 Vpc 20 °C:18.1 A ,210 W
Current/Power for 10.0 h back-up time 1.80 Vpc 20 °C :15.0 A ,174 W
Current/Power for 20.0 h back-up time 1.80 Vpc 20 °C :8.3 A ,93 W
Conversion to capacity at 25 °C (77 °F) : 20 °C Ah x 1,03 (t > 1 h)
Internal resistance (± 10%) to IEC/EN 608 - show phone - :3.6 m
Short circuit current (± 10%) to IEC/EN 608 - show phone - :3.3 kA
Self discharge at 20 °C to IEC/EN 608 - show phone - :max. 3% / month
Heat loss during float service at 20 °C :0.90 W

Mechanical Data

Weight ready for use :63.8 kg
Height of monobloc :323 mm
Height over gas collection system GCS™ :338 mm
Height over terminal connector :351 mm
Width :125 mm
Depth :558 mm
Number of terminals :1/1
Dimension of connector screw hole :M8
Suggested/maximum cable cross-section :(50 mm²/70 mm² *)
Connection torque :8 Nm
Terminal insulation class according to IEC/EN 60529 : IP20
Diameter of diagnostic hole for voltage probe :2.5/5 mm
Connector (copper, tin-coated) rigid and insulated :40/80 mm²
Complete connector and terminal connection accessoires : available (as 48 V/60 V-Set)
Environmental Data :Shelves, cabinets and racks available upon request
Installation :vertically/horizontally
Distance for cooling and ventilation (preset with the rigid connectors) :10 mm
Flame retardancy rating case/cover according to
Underwriters Laboratories (UL) USA : ABS-PC – UL 94 V-0 with LOI > 32%, halogen-free
Flame barriers at vents :installed
Gas collection system GCS™ UL V-0 quality : available upon request
UL file number : ®MH 26065
Service life expected at 20 °C :15 years